Cooling towers offer a proven and cost-effective solution for rejecting heat from condenser water and industrial processes. To maximize the operating cost savings, the fill media—the heat transfer surface that the water flows over—must be properly designed and in good condition.

With competitive price and timely delivery, Longzhuo sincerely hope to be your supplier and partner.

The fill is the heart of the system, and the performance of the entire system depends on maximizing the surface area of fill, evenly distributing the water across the surfaces, and optimizing the thickness of the water film to perform efficiently. 

After years of operation, the fill media can eventually degrade to the point where it must be replaced. Building owners and operators can find it difficult to evaluate the claims by various manufacturers about which type of replacement fill is the best choice.

Which Fill is Better?

The ideal way to understand what fill is optimal is through independent research rather than relying on manufacturers promoting their own product. The most objective evaluation would come from an unbiased side-by-side comparison, in a real-life operational situation. The competing products would be observed for years to determine not only how well they perform at the time of installation, but how they stand up over time. 

Background

This is exactly what happened when a large professional sports arena in Southern California replaced the fill in its cooling towers. Three Baltimore Aircoil Company (BAC) Series Cooling Towers with a crossflow design had been contributing to the comfort and safety of the patrons of the 20,000-seat arena for 18 years. The cooling towers were performing adequately, but due to their age, it was decided that the fill should be replaced as part of a long-term maintenance plan. 

Hanging Fill vs. Block Fill

The plan was to replace the fill pack in one cooling tower per year, rather than taking all three towers off-line at once. In the first tower, and then in the second tower a year later, the fill was replaced with BAC’s VersaCross Replacement Fill, a “hanging” style fill that matched the fill originally installed. When it came time to replace the fill in the third tower, the building owner decided to use a competitive product, a “block” style fill.  

The BAC Series Cooling Tower has a crossflow design, meaning that the water flows vertically down the fill as air flows horizontally across it. Hot water from the system enters the cooling tower and is distributed over the fill (heat transfer surface). Air is drawn through the fill, causing a small portion of the water to evaporate. This evaporation removes heat from the remaining water, which is collected in the cold water basin and returned to the system to absorb more heat. The BAC Series Cooling Tower was designed to use hanging sheet fill, and BAC VersaCross Replacement Fill is the replacement OEM hanging fill on the market. Long continuous sheets, with patterns embossed to increase surface area, are hung to allow smooth water flow from top to bottom. 

The block-style replacement fill is a fundamentally different design. Blocks are comprised of corrugated layers of PVC sheets, with wavy sheets sandwiched between layers of flat sheets. The 12 x 12 x 42-inch blocks are stacked vertically.

The company is the world’s best cooling tower fill supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.

Initial Hesitations About Block Fill

BAC raised concerns about whether the block style fill would perform adequately and whether it was compatible with the Series Cooling Tower design. The vertical spacing of block fill is wider than BAC hanging fill, providing less physical surface area than hanging fill. Reduced surface area results in less evaporative cooling.

Another concern was that water would not flow smoothly and evenly through the block fill. Within each block, where the corrugated layers are connected to each other, water flow can be impinged. Moreover, the transition between blocks significantly interrupts the flow.

These connections between the flat pieces and the corrugated layers and the transitions between blocks also tend to trap solids. This can lead to scale buildup and fouling, resulting in unacceptable degradation in performance in just a few years.

Testing Plan to Compare Performance

After discussion among the building ownership and the installation contractor, the parties agreed that the block fill would be installed and an independent testing company, American Air Balance Co., would be retained by the arena owner to conduct tests comparing the performance of the cell with the block fill to the performance of one of the cells with the VersaCross Fill.

The thermal testing was performed shortly after the block fill was installed. The chosen time was during a Saturday night NHL game because the arena was packed and the spectators were generating a lot of heat. All three cooling towers were running at full speed.

Test Results Showed Clear Difference in Performance

When the two cooling towers were tested, Cooling Tower 1 (CT-1) with block fill performed at 72% of the original fill’s thermal capacity, and Cooling Tower 2 (CT-2) with the VersaCross Fill performed at 96% of the original fill’s thermal capacity.

What should you consider when purchasing a cooling tower?



  1. The structural materials of the cooling tower must be stable, durable, corrosion-resistant, and assembled accurately.
  2. Uniform water distribution, less wall flow, reasonable selection of splashing devices, and not easy to block. 
  3. The cooling tower water spray filler type meets the water quality and water temperature requirements.
  4. The fans are matched to ensure long-term normal operation without vibration and abnormal noise.
  5. Cooling towers should be avoided being placed near heat sources, waste gas and flue gas generation points, chemical storage areas, and coal piles.
  6. The distance between cooling towers or between towers and other buildings should consider not only the towers' ventilation requirements and the interaction between them but also the safe distances for fire protection and explosion prevention of the buildings and the cooling towers' construction and maintenance requirements.
  7. The selected water pump should be matched with the cooling tower to ensure flow, head, and other process requirements.
  8. When selecting multiple cooling towers, choose the same model if possible.

The Lesintor cooling tower body is made of FRP composite material. The surface rubber farmers use imported raw materials. The color contains an anti-UV stabilizer. The surface is smooth, resistant to aging, and particularly shiny over time. 

Motor: It adopts a fully sealed cooling tower special motor, 380v3Ø50HZ, with good waterproof performance and can be safely used in high-temperature environments.

If you want to learn more, please visit our website grp water tank.

Filling: Circular counter-flow filling has a large heat dissipation area increase coefficient, good water flow distribution, large movement of water vapor relative to the surface, and high heat dissipation performance.