Rows of coil selection
thread403- Forum Search FAQs Links MVPsForum
Search
FAQs
Links
MVPs
(Mechanical)
(OP)
3 Nov 14 04:48
Hi Experts,
What should be parameters for a no of coils decision for a AHU.
As the coil no increases from 4 to 6 or 8, the gap becomes less and can cause a high bypass factor.
What implications should be taken care while the no of rows is decided.
Thanks in advance.
Manu
(Mechanical)
3 Nov 14 08:17Sensible heat capacity becomes less as the number of coil rows increase.
(Mechanical)
(OP)
Want more information on custom how to make a heat coil supplier? Feel free to contact us.
3 Nov 14 10:32Given the area/space larger no of coils will increase the capacity, as I believe.
How does that connect to the sensible heat capacity that too inversely.
Manu
(Mechanical)
4 Nov 14 11:00More coil rows increase air contact time and remove more moisture.
(Mechanical)
4 Nov 14 11:23More coils also means more air pressure drop and more work for the fan(s). Keep an eye on the coil face velocity, rule-of-thumb is <= 500 FPM, but check with coil manufacturer. (You don't want to blow condensed water back into the air stream.)
Bill
(Mechanical)
(OP)
4 Nov 14 23:18So would it be correct to understand that In a coil where more rows are available will be for the Latent heat removal or dehumidification. Will the both section be available in the same frame of the coil or the coils for sensible and dehumidification are different set of coils with their respective rows and spacing accordingly.
(Mechanical)
5 Nov 14 11:54Yes more rows will mean more moisture removal, it also means more sensible cooling and a lower discharge air temperature. And as I mentioned earlier more pressure drop for the fan(s) to overcome resulting in a less efficient system.
The number of rows you have is not the only variable in selecting a coil. You need to also consider number of fins per inch, fin material and whether or not protective coatings are needed. All these will impact a coil's capacity to one degree or another (increasing or decreasing the capacity). For example you may be able to reduce the number of rows by increasing the number of fins per inch or using a different fin material.
The best advice I can give you is to take your load calculations, air flow rate, and any special requirements (i.e. coatings or size limitations) to a manufacturer's representative and work with him/her to select a coil to match your needs.
There is to my knowledge no magical equation to determine the best coil design, number of rows, fins per inch, etc. Each coil manufacturer can vary these to provide the amount of cooling you need.
(Mechanical)
7 Nov 14 00:56More rows and fins per inch is more air pressure drop but more efficient sensible heat transfer. For the best dehumidification, you want a low apparatus dew point and a higher coil bypass factor. This means less rows and fins per inch; colder chilled water.
(Mechanical)
7 Nov 14 14:59The amount of moisture removed also depends on how the coil is circuited. There are too many variables to make a definitive statement on how many rows to use. There are plenty of coil design programs available on the internet, where you can evaluate the performance of several different configurations.
(Mechanical)
9 Nov 14 00:51To clarify, you select a high efficiency coil with 14 fins per inch (fpi) that gives saturated outlet conditions. If you can find a coil that gives the same outlet temperature at 8 fpi, you have better dehumidification...
Please let us know here why this post is inappropriate. Reasons such as off-topic, duplicates, flames, illegal, vulgar, or students posting their homework.
Thank you for helping keep Eng-Tips Forums free from inappropriate posts.
The Eng-Tips staff will check this out and take appropriate action.
Click Here to join Eng-Tips and talk with other members! Already a Member? Login
Flatten one end and solder it up. Then fill the whole length with kiln dried fine sand. Then solder a cap on the end. Now you need a former, wood will do, drill a hole in the flattened end and screw or bolt it to the former. Then use a blow torch to heat it up as you bend it around the former. Afterwards you just cut the ends off and pour out the sand. You can clean the inside using a suitable sized bottle brush, just attach a long enough bit of string and pull it through. A tip I was shown years ago for getting a pull string through pipe conduit is to tie a piece of foam to the end of the string, shove it in one end of the pipe, then use a vacuum cleaner on the other end of the pipe to suck the foam through with strinng attached. Have done this with 15mm and it works well, dont see why it wouldnt work with 22.
If you are looking for more details, kindly visit custom induction furnace capacitor supplier.