SHELL AND TUBE HEAT EXCHANGERS

The remainder of this section concentrates on exchangers that are covered by the TEMA Standard.

If you are looking for more details, kindly visit gtboiler.

Rear Header'this is where the tubeside fluid leaves the exchanger or where it is returned to the front header in exchangers with multiple tubeside passes.

Front Header'this is where the fluid enters the tubeside of the exchanger. It is sometimes referred to as the Stationary Header.

A shell and tube exchanger consists of a number of tubes mounted inside a cylindrical shell. Figure 1 illustrates a typical unit that may be found in a petrochemical plant. Two fluids can exchange heat, one fluid flows over the outside of the tubes while the second fluid flows through the tubes. The fluids can be single or two phase and can flow in a parallel or a cross/counter flow arrangement.

Regardless of the type of industry the exchanger is to be used in there are a number of common features (see Condensers ).

those that are used in the power industry such as feedwater heaters and power plant condensers.

those that are used in the petrochemical industry which tend to be covered by standards from TEMA, Tubular Exchanger Manufacturers Association (see TEMA Standards );

Shell and Tube Heat Exchangers are one of the most popular types of exchanger due to the flexibility the designer has to allow for a wide range of pressures and temperatures. There are two main categories of Shell and Tube exchanger :

The main components of a shell and tube exchanger are shown in Figure 2 a, b and c and described in Table 1 .

Many combinations of front header, shell and rear header can be made. The most common combinations for an E-Type Shell are given in Table 2 but other combinations are also used.

The popularity of shell and tube exchangers has resulted in a standard nomenclature being developed for their designation and use by the Tubular Exchanger Manufactures Association (TEMA). This nomenclature is defined in terms letters and diagrams. The first letter describes the front header type, the second letter the shell type and the third letter the rear header type. Figure 2 shows examples of a BEM, CFU, and AES exchangers while Figure 3 illustrates the full TEMA nomenclature.

This is the cheapest of all removable bundle designs, but is generally slightly more expensive than a fixed tubesheet design at low pressures.

If large temperature differences exist between the shell and tube materials, it may be necessary to incorporate an expansion bellows in the shell, to eliminate excessive stresses caused by expansion. Such bellows are often a source of weakness and failure in operation. In circumstances where the consequences of failure are particularly grave U-Tube or Floating Header units are normally used.

In a fixed tubesheet exchanger, the tubesheet is welded to the shell. This results in a simple and economical construction and the tube bores can be cleaned mechanically or chemically. However, the outside surfaces of the tubes are inaccessible except to chemical cleaning.

In a U-Tube exchanger any of the front header types may be used and the rear header is normally a M-Type. The U-tubes permit unlimited thermal expansion, the tube bundle can be removed for cleaning and small bundle to shell clearances can be achieved. However, since internal cleaning of the tubes by mechanical means is difficult, it is normal only to use this type where the tube side fluids are clean.

Floating Head Exchanger (P, S, T and W Type Rear Headers)

In this type of exchanger the tubesheet at the Rear Header end is not welded to the shell but allowed to move or float. The tubesheet at the Front Header (tube side fluid inlet end) is of a larger diameter than the shell and is sealed in a similar manner to that used in the fixed tubesheet design. The tubesheet at the rear header end of the shell is of slightly smaller diameter than the shell, allowing the bundle to be pulled through the shell. The use of a floating head means that thermal expansion can be allowed for and the tube bundle can be removed for cleaning. There are several rear header types that can be used but the S-Type Rear Head is the most popular. A floating head exchanger is suitable for the rigorous duties associated with high temperatures and pressures but is more expensive (typically of order of 25% for carbon steel construction) than the equivalent fixed tubesheet exchanger.

Considering each header and shell type in turn:

A-Type front header

This type of header is easy to repair and replace. It also gives access to the tubes for cleaning or repair without having to disturb the pipe work. It does however have two seals (one between the tube sheet and header and the other between the header and the end plate). This increases the risk of leakage and the cost of the header over a B-Type Front Header.

B-Type front header

This is the cheapest type of front header. It also is more suitable than the A-Type Front Header for high pressure duties because the header has only one seal. A disadvantage is that to gain access to the tubes requires disturbance to the pipe work in order to remove the header.

C-Type front header

This type of header is for high pressure applications (>100 bar). It does allow access to the tube without disturbing the pipe work but is difficult to repair and replace because the tube bundle is an integral part of the header.

D-Type front header

This is the most expensive type of front header. It is for very high pressures (> 150 bar). It does allow access to the tubes without disturbing the pipe work but is difficult to repair and replace because the tube bundle is an integral part of the header.

N-Type front header

The advantage of this type of header is that the tubes can be accessed without disturbing the pipe work and it is cheaper than an A-Type Front Header. However, they are difficult to maintain and replace as the header and tube sheet are an integral part of the shell.

Y-Type front header

Strictly speaking this is not a TEMA designated type but is generally recognized. It can be used as a front or rear header and is used when the exchanger is to be used in a pipe line. It is cheaper than other types of headers as it reduces piping costs. It is mainly used with single tube pass units although with suitable partitioning any odd number of passes can be allowed.

E-Type shell

This is most commonly used shell type, suitable for most duties and applications. Other shell types only tend to be used for special duties or applications.

F-Type shell

This is generally used when pure countercurrent flow is required in a two tube side pass unit. This is achieved by having two shells side passes'the two passes being separated by a longitudinal baffle. The main problem with this type of unit is thermal and hydraulic leakage across this longitudinal baffle unless special precautions are taken.

G-Type shell

This is used for horizontal thermosyphon reboilers and applications where the shellside pressure drop needs to be kept small. This is achieved by splitting the shellside flow.

H-Type shell

This is used for similar applications to G-Type Shell but tends to be used when larger units are required.

J-Type shell

This tends to be used when the maximum allowable pressure drop is exceeded in an E-Type Shell even when double segmental baffles are used. It is also used when tube vibration is a problem. The divided flow on the shellside reduces the flow velocities over the tubes and hence reduces the pressure drop and the likelihood of tube vibration. When there are two inlet nozzles and one outlet nozzle this is sometimes referred to as an I-Type Shell.

K-Type shell

This is used only for reboilers to provide a large disengagement space in order to minimize shellside liquid carry over. Alternatively a K-Type Shell may be used as a chiller. In this case the main process is to cool the tube side fluid by boiling a fluid on the shellside.

X-Type shell

This is used if the maximum shellside pressure drop is exceeded by all other shell and baffle type combinations. The main applications are shellside condensers and gas coolers.

L-Type rear header

This type of header is for use with fixed tubesheets only, since the tubesheet is welded to the shell and access to the outside of the tubes is not possible. The main advantages of this type of header are that access can be gained to the inside of the tubes without having to remove any pipework and the bundle to shell clearances are small. The main disadvantage is that a bellows or an expansion roll are required to allow for large thermal expansions and this limits the permitted operating temperature and pressure.

M-Type rear header

This type of header is similar to the L-Type Rear Header but it is slightly cheaper. However, the header has to be removed to gain access to the inside of the tubes. Again, special measures have to be taken to cope with large thermal expansions and this limits the permitted operating temperature and pressure.

N-Type rear header

The advantage of this type of header is that the tubes can be accessed without disturbing the pipe work. However, they are difficult to maintain and replace since the header and tube sheet are an integral part of the shell.

P-Type rear header

This is an outside packed floating rear header. It is, in theory, a low cost floating head design which allows access to the inside of the tubes for cleaning and also allows the bundle to be removed for cleaning. The main problems with this type of header are:

  • large bundle to shell clearances required in order to pull the bundle;

    Are you interested in learning more about Industrial Finned Tube Heat Exchanger? Contact us today to secure an expert consultation!

  • it is limited to low pressure nonhazardous fluids, because it is possible for the shellside fluid to leak via the packing rings;

  • only small thermal expansions are permitted.

In practice it is not a low cost design, because the shell has to be rolled to small tolerances for the packing to be effective.

S-Type rear header

This is a floating rear header with backing device. It is the most expensive of the floating head types but does allow the bundle to be removed and unlimited thermal expansion is possible. It also has smaller shell to bundle clearances than the other floating head types. However, it is difficult to dismantle for bundle pulling and the shell diameter and bundle to shell clearances are larger than for fixed head type exchangers.

T-Type rear header

This is a pull through floating head. It is cheaper and easier to remove the bundle than with the S-Type Rear Header, but still allows for unlimited thermal expansion. It does, however, have the largest bundle to shell clearance of all the floating head types and is more expensive than fixed header and U-tube types.

U-tube

This is the cheapest of all removable bundle designs, but is generally slightly more expensive than a fixed tubesheet design at low pressures. However, it permits unlimited thermal expansion, allows the bundle to be removed to clean the outside of the tubes, has the tightest bundle to shell clearances and is the simplest design. A disadvantage of the U-tube design is that it cannot normally have pure counterflow unless an F-Type Shell is used. Also, U-tube designs are limited to even numbers of tube passes.

W-Type rear header

This is a packed floating tubesheet with lantern ring. It is the cheapest of the floating head designs, allows for unlimited thermal expansion and allows the tube bundle to be removed for cleaning. The main problems with this type of head are:

  • the large bundle to shell clearances required to pull the bundle and;

  • the limitation to low pressure nonhazardous fluids (because it is possible for both the fluids to leak via the packing rings).

It is also possible for the shell and tube side fluids to become mixed if leakage occurs.

Heat exchanger maintenance procedure

What is heat exchanger maintenance ?

The heat exchanger maintenance consists in cleaning the bundle of inner tubes and the outer cleaning of the cloak.

The maintenance procedure is carried out in three phases:

What is a heat exchanger ?

A heat exchanger is an apparatus where the exchange of heat energy occurs between two different fluids at different temperatures.
The most used  is what is known as 'tubular beam and cloak exchanger', as its large surface structure allows to exchange large quantities of heat.
This type of exchanger has a cylindrical shape, formed by a container called the mantle, where a bundle of tubes passes through each of them, both of which are crossed by the fluids.

The most common malfunction is called Fouling.

heat exchanger maintenance

Fouling is the deposit of solid material inside the pipes, transported by fluids or precipitation products such as limestone, this clogging of the pipes leads to a reduction in the heat transfer coefficient and in conclusion a worse performance of the exchanger itself.

What to do?

Periodically maintain a heat exchanger maintenance.

1 ' Tube bundle extraction procedure

The bundle extractor or bundle puller consists in extracting the exchanger from its shell through the
Ad hoc machines, called aerial tube bundle extractor having a variable pull power, depending on the size of the exchanger itself.

2 ' Tube bundle transport procedure

The tube bundle transport procedure can be carried out in two different ways, depending on the height where the exchanger is located.
For large heights the transport will be carried out first by using cranes and later with ad hoc called straddle carrier cars, for lower heights it would be enough to use truck mounted or self propelled.

Click on it fo more information about bundle transport

3 ' Tube bundle cleaning procedure

The cleaning process of the tube bundles consists of the pulp of the same thanks to robots that wash away the deposits both internally and externally, through high pressure jet jets.

Click on it fo more information about bundle cleaning

4 ' Tube insertion procedure

The insertion of the bundle consists in re-inserting the exchanger into its own shell through the aerial bundle extractor  themselves after the cleaning phase.

What is the Bundle Extractor Procedure ?

The Bundle Extractor or bundle puller procedure is the first phase of one of the four processes for maintaining the heat exchanger, which has as its purpose the output of the tube bundle from its shell.

This first step is done by means of ad hoc machines called tube bundle extractors.

Idrojet srl. has designed different types of extractors those equipped with cranes called aerial bundle extractors and those without these truck mounted, both for the same purpose but used for different cases based on the location of the heat exchanger.

For heights above 7 mt, the bundle puller used are airplanes, and by means of an extruder crane are positioned to the desired height.

Less than 7 meters long, Idrojet srl  has produced self-propelled and truck mounted  which allow not only to extract the tube bundle without the use of any external crane, but to transport it autonomously by avoiding the use of the straddle carrier, saving so much time and money, so a single car for the first and second stages.

Tube bundle Insertion last step

The first step and last step, is the insertion, are carried out with the same bundle extractors.

Below an example of heat exchanger maintance where tube bundle insertion after the heat exchanger cleaning procedure ' watch it below.

If you want rental the bundle extractor visit www.idmitaly.com

Contact us to discuss your requirements of Hot Water Boiler. Our experienced sales team can help you identify the options that best suit your needs.