Cooling Tower Counterflow Fill Media Review - Brentwood Industries

It’s important to regularly touch base on the basics of cooling towers to provide anyone new to the industry with vital information, but it’s also a good reminder for those who have been in the industry for many years. There are three basic flute geometry designs for modular film fills: cross flutes (CF), offset-vertical flutes (OF), and vertical flutes (VF). Each geometry has its own set of advantages and disadvantages in relation to fouling resistance and thermal performance.

Goto Longzhuo to know more.


Cross Flutes
Cross-fluted designs have been the industry standard for over 30 years. The nominal 30° from vertical flute orientation – 60° angle included between flutes on adjacent sheets – maximizes turbulence and air-water mixing, and high rates of heat transfer are created in relatively shallow fill sections (6’ and less).

Another important feature is this geometry’s ability to redistribute the falling water laterally so that a multi-layer fill section made up of alternating horizontal rows can fully “wet-out” the entire packed volume. This makes the cross-fluted geometry very thermally efficient but not very resistant to fouling. Because of the angled flutes, water film velocity is slowed and deposition of solids can readily occur. It is for this reason that Brentwood discourages CF fills in water that has a high degree of fouling potential.


Offset-Vertical Flutes
Like CF fills, the offset-vertical flute geometry allows for a high degree of air-water turbulence, and therefore, high heat transfer rates. A differentiating factor between the two fill types is that offset-fluted fills offer lower airside airflow resistance (pressure drop) than CF fills. The vertically oriented flutes allow for high water film velocity, thus allowing for a higher degree of fouling resistance than CF fills. Since the flutes are offset, the water can migrate laterally, as it does in CF fills, but to a lesser degree. For highly fouling water, however, OF designs should be considered only if achieving maximum thermal performance is required.


Vertical Flutes
Vertically oriented flute geometry allows the highest water film velocity and the highest degree of fouling resistance. New VF designs allow for high heat transfer rates but not as high as those of CF and OF designs. The high velocity water film significantly reduces the attachment of slime-forming bacteria, and therefore, the accumulation of silt. This type of media is recommended by Brentwood when the source water has strong fouling potential and thermal performance can be compromised.

The above references are for counterflow fill designs and their macro-structure. The same basics can be applied to film fills as well as for newer modular splash packs, or trickle packs. There has been a recent uptick in the requests for information regarding the fouling potential between a cross-fluted designed trickle pack and an offset vertical designed splash pack, like the HTP25. Even though these products may look very anti-fouling, the underlying principles of why packs foul is still at play. Cross-fluted designs still increase thermal performance at the expense of water velocity through the packs as compared to a vertically offset design due to the reduced water velocity and corresponding shear stresses.

Future blogs will dive deeper into fouling and we will be sharing some preliminary results from the Brentwood R&D fouling chamber, so keep an eye out!

How To Pick A Cooling Tower: Crossflow Versus Counterflow —

By Chad Edmondson

Cooling towers for HVAC systems come in either crossflow or counterflow configurations. This is defined by the way the water meets the heat transfer surface, more commonly known as the “fill” surface. Crossflow cooling towers distribute the hot water perpendicularly to the air flow. Water flows from the top of the cooling tower through the hot water gravity distribution basin and into the fill while the cooling tower fan draws air horizontally across the fill. Counterflow cooling towers also distribute water from the top of the tower thru pressurized spray nozzles, however the air flow is parallel (but in opposing direction) to the flow of water. Air is drawn from the bottom of the cooling tower, passing over the fill surface and exiting out the top.

The obvious question is: Why would one specify one type of cooling tower configuration over the other?

Very simply, it typically comes down to footprint. In most cases, a crossflow tower is preferred for several reasons that include, most importantly, overall efficiency and serviceability. However, crossflow towers have a larger footprint so if you are limited in real estate, a counterflow tower, which is taller but has a smaller footprint, may be your only option.   A counterflow tower could also be a better option because of its air intake configurations if you are installing the tower next to one or more walls.

Now let’s explore the design characteristics of each type of tower.

Crossflow Towers

Serviceability is a big bonus when it comes to crossflow towers. Crossflow towers have an internal access plenum that can be fitted with an internal platform from which the drive system can be serviced, and the entire fill assembly inspected. These towers can also be fitted with an external service platform or a ladder with handrails that provides safe maintenance access to the hot water basin.

Are you interested in learning more about smc water tank? Contact us today to secure an expert consultation!

Water flow from the top of a crossflow tower is by gravity only. The spray nozzles do not require any additional pressurization, which saves pump energy. At reduced water flow rates, weir dams help to fully distribute the water across the fill surface.  Counterflow towers, however, require pressurized spray nozzles to ensure even distribution of water at part load.

This is an important distinction to remember since ASHRAE 90.1- requires that chiller systems be configured either with multiple or variable speed condenser water pumps so that the cooling tower can be operated:

(1)  With flow that is produced by the smallest pump at its minimum expected flow rate, or 

(2)  At 50% of design flow per cell.

The intent of this requirement is to improve energy efficiency by maximizing the number of towers operating for a given flow rate while also maintaining the minimum required flow rate through the tower.  This is because it is more efficient to run a single 500 ton chiller across two 500 ton towers. More tower tonnage means more heat transfer surface, which increases the amount of evaporative cooling. 

The challenge is reducing flow without risking insufficient water distribution across the fill. Dry areas across the heat transfer surface are bad for two reasons:

(1) Dry areas create less resistance to air flow, so more air will flow over dry areas than wet areas, which limits the potential for evaporative cooling

(2) Dry areas tend to increase the amount of mineral deposits that get left behind from evaporated water, increasing the potential for dry air disease. [Link to  Cooling Tower and Condenser Water Design Part 11: Avoiding Common Pitfalls.]

Counterflow Towers

In addition to being taller and more compact than crossflow towers, counterflow towers have pressurized hot water nozzles which increases the pump head requirement and total system operating costs. Counterflow towers also have limited internal accessibility for service and inspection.  An external service platform and ladder is usually required for access to the hot water spray distribution and drive system.

To operate a counterflow cooling tower at half flow you will probably need to modify the spray nozzle pattern to ensure a fully wetted fill.  Of course, before lowering the flow through any cooling tower, you should always check with the manufacturer to determine what the minimum required flow is. Otherwise, you run the risk of underflowing the tower and eventually building up scale on heat transfer surfaces.

(Note: All the above features and benefits primarily apply to factory assembled cooling towers, not field erected cooling towers.)

Fan Options for Cross and Counterflow Towers

Both cross and counterflow towers can be built with either axial or centrifugal fans. For indoor applications and/or those with extremely low height requirements, centrifugal fans can be used on counterflow towers to keep the vertical height of the overall unit to a minimum. This option, however, is typically limited to smaller applications that are 272 tons or less and under USGPM.