Generator Ratings Explained

29, Jul. 2024

 

Generator Ratings Explained

 Definitions

Term Definition Intermittent Power The highest output obtainable at SAE standard ambient conditions. These levels may be only maintained for operating periods of short duration Standby Power The electrical output of a generator set used for emergency or backup power, for use when normal powerline utilities fail. Usually runs less than 60 hours per year. Continuous Power The output which can be obtained at SAE standard ambient conditions, operating in a continuous duty mode. The electrical load on the generator set will usually be steady. Prime Power The electrical output of a generator set used as the primary source of power, often running 24 hours a day. The electrical load usually varies. pf ' Power Factor
  • Three phase circuits will usually assume a 'power factor' (p.f.) of 0.8 lagging.
  • The concept of power factor can get a bit confusing but basically it refers to the out-of-phase relationship between the voltage and the current in an electrical system.
  • If actual data are not available, a p.f. of 0.8 is assumed and the power is shown in kiloVolt/Amperes (kVA).
  • There is a direct relationship between the voltage (V), the current (A), and the power in kW or in kVA.
  • The assumption of a 0.8 lagging power factor for three phase circuits is not necessarily a safe assumption. This may be 'typical', if typical exists, of inductive reactance loads such as motors. However, many three phase circuits now incorporate non-linear loads such as variable frequency drives that require special attention to correctly size the generator to the load characteristics. Similarly, assuming a 1.0 (unity) power factor for single phase circuits may not always be correct.
kW ' kilowatts

kW, kilowatts, or sometimes kWm, kilowatts mechanical, refers to the power output from an engine driving a generator set or, in other words, the mechanical power driving the generator.

Link to YuchaiHI

To avoid confusion, the electrical output from the generator is often referred to as kWe (or ekW) which is the actual generator output after efficiency losses within the generator. Electrical power is usually measured in Watts (W) or thousands of Watts (kilowatts, kWe). kWe is sometimes referred to as 'real power' while kVA (kilovolt-amperes) is apparent power.

For single phase circuits the relationship is: Amperes x Volts ÷ 1,000 = kW.

For three phase circuits: Volts x 1.73 x Amperes ÷ 1,000 = kVA

If you know the electrical load in Amps and you know the system voltage, you can find the required kilowatts or kVA from the chart. Similarly, the system's current can easily be found if you know the kWe and voltage.

Are you interested in learning more about 450 Kw Standby Generator? Contact us today to secure an expert consultation!

Sizing a Generator Set

Before attempting to size a generator set, gather as much detail about the actual operating conditions and loads as possible. Sometimes a custom-built generator set'sized for the specific requirements'can easily pay for its cost in fuel savings, especially where motor starting is a primary consideration.

The following charts are handy guides to find the current (amperes) or kilowatts in an electrical system.

Generator Ratings in Amperes for 3 Phase Outputs at 0.8 Power Factor
KVA KWe 208V 220V 240V 380V 416V 440V 480V 600V 6.3 5 17.5 16.5 15.2 9.6 8.6 8.3 7.6 6.1 9.4 7.5 26.1 24.7 22.6 14.3 13 12.3 11.3 9.1 12.5 10 34.7 33 30.1 19.2 17.3 16.6 15.1 12 18.7 15 52 49.5 45 28.8 26 24.9 22.5 18 25 20 69.5 66 60.2 38.4 43.7 33.2 30.1 24.1 31.3 25 87 82.5 75.5 48 52 41.5 37.8 30.2 37.5 30 104 99 90.3 57.6 62.5 49.8 45.2 36.1 43.8 35 125 118 108 68 70 59 54 42.2 50 40 139 131 120 76 78 66 60 48 56.3 45 156 147 135 86 86 74 68 54 62.5 50 173 165 152 96 104 83 76 60 75 60 208 198 181 115 130 99.6 91 72 93.8 75 261 247 226 143 139 123 113 90 100 80 278 264 240 154 173 133 120 96 125 100 347 330 301 192 217 166 150 120 156 125 433 413 375 240 260 208 188 150 187 150 520 495 450 288 304 249 225 180 219 175 608 577 527 335 347 289 264 211 250 200 694 660 601 384 434 332 301 241 312 250 866 825 751 480 521 415 376 301 375 300 990 903 576 607 498 451 361 438 350 672 694 581 527 422 500 400 770 868 665 602 482 625 500 960 868 830 752 602

1) Formula used is A = (KVA x ) / (1.73 x Volts)
2) Current ratings are 'linear'. For example, a 750 KVa (600 kWe at 0.8 Power Factor) at 480V produces 902 amps, or double the what is shown in the table for 375 kVa

*NEMA Starting Codes for Three Phase Motors KVA / HP Required for Locked Rotor Starting
Code Starting KVA /HP § Typical Motor Size A 0 ' 3.15 (Special) B 3.15 ' 3.55 (Special) C 3.55 ' 4.0 (Special) D 4.0 ' 4.5 (Special) E 4.5 ' 5.0 (Special) F 5.0 ' 5.6 15 H.P. + G 5.6 ' 6.3 10 H.P. H 6.3 ' 7.1 5 & 7.5 H.P. J 7.1 ' 8.0 3 H.P. K 8.0 ' 9.0 1.5 & 2 H.P. L 9.0 ' 10.0 1 H.P. M 10.0 ' 11.2 < 1 H.P.

* Starting code letter can be found on Motor Name Plate Data. DO NOT confuse 'design code' with 'starting code'.
§ For generator sizing use the higher inrush value. Consult the generator set manufacturer for voltage dip information and for generator current output capability.

Cat Diesel Generators | Industrial Rated Standby & Prime ...

Caterpillar is the world's largest manufacturer of generator sets, offering the largest range of specifications available.  For prime, continuous or standby power service, Cat commercial and industrial diesel generator sets deliver reliable, clean, economical power.

Each Cat diesel generator set is designed, engineered and manufactured for optimal performance. All major components are tested individually; and once the generator set is assembled, the complete unit is tested at and above 100% of rated load for operation and safety.

All gensets have optional weather and sound attenuated enclosures.  Need help sizing your generator or designing a system? 

The company is the world’s best Electric Front Loader supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.