What is the alternative to a check valve?

13, Aug. 2024

 

Why Check Valves Slam and What To Do About It

Check valves are simple valves. They use forward flow to open the valve, then automatically close when flow stops, preventing reverse flow from making its way back through the valve. They don't require power to function, and they don't require a whole lot of attention or maintenance. They do get a lot of attention, however, when they slam.

Huade Hydraulic are exported all over the world and different industries with quality first. Our belief is to provide our customers with more and better high value-added products. Let's create a better future together.

What causes the slam?

A check valve relies on gravity and/or reverse flow to close completely. Opportunity for check valves to slam frequently occurs at pump shutdown. When a pump stops, gravity and reverse flow slam the check valve shut. Because fluid is non-compressible, it creates a pressure or shock wave (water hammer). The fluid continues to flow back and forth until friction losses cause the wave to settle.

Slamming check valves cause serious pressure surges in a system that rattle pipes and damage equipment. Some people assume that's just what check valves do. "No matter what, they're going to slam." But that's just not the case. Usually, the real cause of these problems stems from poor sizing and selection, not the type of valve itself.

Minimizing Slam Through Proper Sizing

Oftentimes check valves are selected based on the pipe size and the desire for the largest Cv possible. (CV stands for 'coefficient of flow' for valves and demonstrates a valve's capacity for liquid to flow through it.) Of course you want the ability to put as much fluid through the valve as possible, right? Makes sense, except this completely disregards the fact that flow conditions determine the internal performance of a check valve because the disc is directly in the flow path.

If there is not enough flow to keep the valve fully open with the disc reaching the ceiling of the check valve, the disc will move up and down, resulting in pre-mature wear, potential for failure, and a higher pressure drop.

For proper check valve selection, consider the following:

  • Line sizing
  • Application data (fluid characteristics, including temperature and pressure)
  • Seat type
  • Installation (horizontal or vertical)
  • End connection
  • Valve rating
  • Material compatibility with the medium
  • Envelope dimensions
  • Leakage requirements

Selecting a valve of the proper size will have an impact on the amount of water hammer felt by the piping system.

Selecting the right type of check valve

Another solution to slamming check valves is to look at the type of check valve used in the application. Silent, ball, and resilient hinge are alternatives to the traditional swing check valve. They each carry different characteristics with varying degrees of pressure drop and closure speed.

Silent Check Valves

Silent or spring 'assisted check valves do not rely on gravity or reverse flow to close. Instead, the spring closes in about one-tenth of a second, the valve before reverse flow has an opportunity to slam the valve shut. It is able to close quickly because it has a shorter distance to travel than the flap on a traditional check valve.

This video from DFT illustrates how pressure spikes in the system are greatly reduced with a silent check valve.

Ball Check Valves

Ball check valves are economical and very simple valves. They sometimes utilize a rubber coated ball that floats up and out of the way while flow passes through the valve, and seats when flow stops. This particular valve closes slowly, so the potential for slamming is high.

There are other styles of ball check valves that work similarly to silent or in-line check valves. These are called cone check valves. 

Resilient Hinge Check Valves

Resilient hinge check valves are very similar to the traditional swing check valve. The major difference is that a rubber molded disc flexes up and out of the way when fluid flows through the valve. The flap does not rotate around a hinge pin.

It has a shorter stroke than a traditional swing check valve, reducing the closing time of the valve and minimizing the potential for water hammer to occur.

Conclusion

Each of these valves have different characteristics, features and benefits that should be carefully selected for just the right fit into a system. If you're experiencing issues with a check valve or need to select a new one for your process, talk to an engineer experienced in selection/sizing of these valves. Doing so will help your system perform at its highest efficiency while reducing slam and requiring less maintenance.

Backflow Preventer vs. Check Valve: What's the Difference?

Backflow preventers offer the best protection against contamination of city water supplies

A check valve provides a basic form of backflow prevention, preventing water from flowing in the wrong direction. National Fire Protection Association (NFPA) model codes and standards require them in various places on fire protection systems, and check valves are essential components of backflow preventers. But they are not adequate on their own to protect potable city water supplies from backflow contamination. 'Potable' supplies contain treated, drinking-quality water.

In this blog, we explain the key differences between backflow preventers vs. check valves. And we clear up a misconception that's often inquired about in online forums: while check valves have other important applications, they cannot be considered a safe substitute for backflow preventers when it comes to protecting the purity of drinking water.

In the market for check valves or check key tools for backflow preventers? Be sure to check out our selection of check valves. QRFS also carries backflow check key tools and toolsets, which quickly remove or install cam checks found in Ames and Watts backflow prevention assemblies.

Are you interested in learning more about Right Angle Check Valve? Contact us today to secure an expert consultation!

Check valves vs. backflow preventers: why they aren't interchangeable devices

Backflow occurs when pressure changes in pipes cause the flow of liquids, gas, or semisolids to reverse in the wrong direction. Check valves are designed to ensure substances in a pipe only flow one way, automatically closing to prevent unwanted backflow if the direction is reversed. They are used successfully in a wide variety of applications: protecting equipment such as pumps and filters from backflow damage, stopping drainage in a fire sprinkler system with elevation changes, providing pressure relief in liquid or pneumatic applications, and more.

Because of their simple design, check valves generally operate without automation or human interaction'continuing to work even if the power goes out or people can't manually cycle them. Instead, they are flow-sensitive; when water flows through a pipe, check valves rely on the water's flow velocity to open or close. The cracking pressure, or minimum upstream pressure needed to operate a check valve, generally falls between 1 and 5 pound-force per square inch (PSI).

Many check valves feature a hinged clapper with a spring that keeps the valve closed until it's opened by water flowing from a source. If the pressure downstream exceeds upstream pressure, the spring presses the clapper against a rubber seat, forming a watertight seal and preventing flow from reversing.

But here's the thing: a check valve can serve as an important means of backflow prevention in low-risk scenarios, such as when equipment damage stands out as the biggest risk. But when the stakes are as high as the purity of the water people drink, local plumbing codes require the more reliable protection of backflow preventers.

While check valves function reliably most of the time, failures can occur for many reasons. Since a check valve's clapper is always in the flow path, clapper movement will happen even if there isn't enough flow. Parts that rub against each other cause wear, which can eventually lead to check valve failures. In extreme cases, damaged components can even escape into the line, causing other valves or equipment to malfunction.

Worn seat seals are another common cause of check valve failures, as well as lodged debris that causes the valve to remain stuck in the open or close position. Damage can also be caused by water hammer, in which flow reversal downstream causes the valve to abruptly close'resulting in a pressure wave that propagates throughout and damages the pipe. Improper maintenance, installation, or assembly can also lead to failures.

Backflow preventers take backflow protection to the next level

Backflow can be dangerous when pressure changes in water pipes cause water from building systems like sprinklers, irrigation, or plumbing to seep back into the main city supply line. When this happens, the public drinking water can be polluted with contaminants like fertilizers, pesticides, human waste, and harmful chemicals.

Backflow can also be extremely expensive to remediate: the Environmental Protection Agency (EPA) states that the average backflow incident takes nearly 500 hours to fix at a cost of $14,800.

Like a check valve, a backflow preventer is a device that ensures water only travels in one direction. Its sole job is to keep water flowing from the water main to a building's pipes. However, it takes backflow protection to the next level with extra fail-safes designed to keep drinking water pure by preventing the non-potable water in a building's systems from backing up and contaminating it.

Our previous blog, 'How Does a Backflow Preventer Work?' offers great detail on the different types of backflow preventers and how they work. It also explains when they're required to protect city water supplies connected to fire protection systems.

Local plumbing codes set forth requirements for backflow preventers in building systems, such as fire protection equipment. They also typically require backflow preventers to be tested regularly and maintained by certified professionals to ensure they are reliable and functioning properly.

Be sure to check with your local water authority to understand specific requirements for backflow preventers in your area.

Fire protection systems: How does a backflow preventer work?

Two main types of backflow preventers are utilized in fire protection systems. Double Check Valve (DCV) backflow preventers are common in low-hazard situations, where cross-contamination might create a nuisance or be aesthetically objectionable but wouldn't create a health hazard.

These backflow preventers are specifically designed to prevent reverse flow in fire sprinkler systems, using two check valves assembled in a series to prevent water from backing up into the supply line.

This redundancy ensures that one check valve will continue to protect the city water supply even if the other fails. The assembly also enables the closure of one valve to reduce the pressure differential across the other, creating a more reliable seal and avoiding even minor backflow leakage.

A Reduced Pressure Zone (RPZ) backflow preventer ups the protection of redundant check valves even more. The addition of a hydraulically operated differential relief valve makes this device essentially fail-safe.

During normal operation of an RPZ backflow preventer, the pressure between the two check valves'referred to as the zone of reduced pressure'is maintained at a lower pressure than the supply pressure. If either check valve should leak, the relief valve is designed to open and discharge water to the outside, ensuring that backflow never occurs.

On fire protection systems, plumbing codes generally require RPZ backflow preventers in high-hazard cross-connections, where hazardous chemicals like antifreeze or corrosion inhibitors could threaten public health if they are introduced into a city's water supply. Some local water authorities, however, require them on all fire protection applications.

Backflow preventers vs. check valves: greater protection is needed for potable water supplies

Check valves are relied on to prevent backflow in a variety of applications, from HVAC systems to sump pumps to fire sprinkler systems with elevation changes. But when it comes to public health and safety, many water authorities and municipalities demand the more reliable protection of backflow preventers to keep drinking water safe.

Knowing key differences between backflow preventers vs. check valves helps property owners and facility managers understand why the added cost and complexity makes sense.

QRFS has a selection of check valves for fire protection and other applications. We also carry backflow check key tools and toolsets, which quickly remove or install cam checks found in Ames and Watts backflow prevention assemblies.