Cooling Tower Selecting, Sizing, and Design

13, May. 2024

 

Cooling Tower Selecting, Sizing, and Design

Find Your Optimal Cooling Tower Type

As the technology leading cooling tower manufacturer, Delta’s cooling tower designs last longer, save on costs and eliminate downtime, which translates to an unrivaled lifecycle. So, there’s no need to worry about replacements. And, Delta’s product quality is backed by a 20-year warranty. To learn more, contact Delta today. Click Here!

Are you interested in learning more about 20 ton cooling tower? Contact us today to secure an expert consultation!

Explore Delta’s Cooling Tower Sizing Calculator

To determine the perfect cooling tower design and size for your needs, Delta makes it easy with our downloadable sizing program. To discover Delta’s cooling tower sizing & selection program, simply click here.

Narrowing Down Your Cooling Tower Selection

If you are interested in learning the methods of determining the proper size cooling tower, rest assured that Delta is here with guidance. Explore our handy information. Click here to learn about sizing & selecting.

Know Your Cooling Tower Capacity Calculation

Whether your application is for industrial process cooling or HVAC condenser cooling, the data required is the same. The following design data is required for cooling tower sizing to properly select the appropriate model:

  • Flow Rate in GPM
  • Range of cooling in °F (T1 – T2)
  • Area Wet Bulb Temperature in °F (Twb)

Cooling Tower Heat Load Calculation

The Design Heat Load is determined by the Flow Rate, and the Range of cooling, and is calculated using the following formula:

Heat Load (BTU/Hr) = GPM X 500 X Range (T1 – T2) °F

If the range of cooling, Heat Load, and one of the other two factors are known (either the GPM or the ° Range of cooling), the other can be calculated using this formula.

  • GPM = Heat Load (BTU/Hr) / 500 X ° Range of cooling
  • ° Range of cooling = Heat Load (BTU/Hr) / 500 X GPM The Design GPM and the °

The range of cooling is directly proportional to the Heat Load.

To learn more, contact Delta today. Click Here! 

Let Us Help You With Cooling Tower Sizing & Selecting

How comfortable are you working up a cooling tower selection?

The cooling tower selection table may look confusing, but after you have made a few selections, the process is straightforward. If you need a refresher, this may help. The following design data is required to select cooling towers:

Flow Rate in GPM

Range of cooling in °F (T1 - T2)

Area Wet Bulb Temperature in °F (Twb)

The Design Heat Load is determined by the Flow Rate, and the Range of cooling, and is calculated using the following formula: Heat Load (BTU/Hr) = GPM X 500 X ° Range of cooling.

More importantly, if the Heat Load and one of the other two factors are known, either the GPM or the ° Range of cooling, the other can be calculated using this formula.

For example: GPM = Heat Load (BTU/Hr), or 500 X ° Range of cooling ° Range of cooling = Heat Load (BTU/Hr) 500 X GPM

So, as you can see, the Design GPM and the ° Range of cooling, are directly proportional to the Heat Load.

And, 500 is the “fluid factor” which is based on water as the heat transfer fluid. The fluid factor is obtained by using the weight of a gallon of water (8.33 lbs.) multiplied by the specific heat of the water (1.0) multiplied by 60 (minutes/hour).

The first step in selecting a cooling tower is to determine the Nominal cooling tower load. Since a cooling tower ton is based on 15,000 BTU/Hr, the formula is:

Nominal Load = GPM X 500 (Constant) X ° Range of cooling, 15,000 BTU/Hr/Ton or, the more simplified version of the same formula, Nominal Load = GPM X ° Range of cooling 30

More on Sizing & Selecting

Examples of Different Applications

Once the Nominal cooling load has been calculated, a Correction Factor must be determined to calculate the Actual Rated cooling tower tons required for the specific conditions of service. The correction factor adjusts for the ease or difficulty of cooling based on the Theoretical Design of all cooling towers.

The Nominal Ton Correction Factor is determined by using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed. Note that the curves are shown as three separate sections. The WET BULB CORRECTION SECTION, the APPROACH SECTION, and the CAPACITY MULTIPLIER FACTOR SECTION. First, find the Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the Range line over to the intersection of the Wet Bulb line.

Now move down along the Wet Bulb line to the APPROACH SECTION, in the lower left-hand section of the chart, and stop at the intersection of the Approach line. Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curves and stop at the intersection of the Range line and read the CAPACITY MULTIPLIER FACTOR.

The Actual Rated cooling tower tons can now be calculated by multiplying the Nominal cooling tons, which was previously calculated, by the CAPACITY MULTIPLIER FACTOR. The Actual Rated cooling tower tons is the capacity required for the specific conditions of service, and the next largest size cooling tower should be selected for the application.

Following are selection examples for three different applications. One example is based on conditions that are identified as "Theoretical Design," for reasons which will become apparent.

The second example, entitled "Actual Design" is a selection based on adjusting from Theoretical to Actual design.

The third example, "Modified Application", converts an actual once-through well water system to a cooling tower recirculation system.

Sizing & Selecting

Read on to Learn about Cooling Tower Selection Procedure

Example 1. Theoretical Design


The following conditions are provided for selection purposes:

The operating water flow rate is 600 GPM.

Hot water temperature (T1) to the cooling tower is 95° F.

Cold water temperature (T2) desired from the cooling tower is 85° F.

The installation location's wet bulb temperature (Twb) is 78° F.

You can now make a cooling tower selection with this information:

The water flow is 600 GPM. The Range of cooling is 10° - (T1 - T2). The Approach to the wet bulb temperature is 7° - (T2 - Twb).

First the cooling tower NOMINAL load has to be determined:

Nominal Load = GPM x 500 x ° Range, = GPM x ° Range, therefore, 15,000 BTU/Hr 30

Nominal Load = 600 gpm x 10° Range = 200 tons of cooling required.

30 Since the Heat Load = Flow (gpm) x 500 x °Range of cooling= 600 gpm x 500 x 10° = 3,000,000 BTU/Hr and a cooling tower nominal ton = 15,000 BTU/Hr, the nominal cooling tower ton is derived from the actual heat load. Therefore, a heat load of 3,000,000 BTU/Hr = 200 nominal cooling tower tons.

Now the Nominal Ton Correction Factor has to be determined for the conditions established:

A 10° Range of cooling, and a 7° Approach to the design wet bulb temperature of 78°F, using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed.

Find the 10° Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the 10° Range line over to the intersection of the 78° Wet Bulb line.

Move down along the 78° Wet Bulb line to the APPROACH SECTION, (the lower left-hand section), and stop at the intersection of the 7° Approach line.

Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curve and stop at the intersection of the 10°Range line, and read the CAPACITY MULTIPLIER FACTOR, which is 1.0.

To select the proper cooling tower for this application, multiply the 200 Nominal tons calculated, by the 1.0 CAPACITY FACTOR. As previously stated, the correction factor adjusts for the ease or difficulty of cooling in relation to the Theoretical Design. So in this case, since the CAPACITY CORRECTION FACTOR is 1.0, the Nominal and Actual Rated tons are the same as the Theoretical Design, and a Model DT-200I cooling tower can be quoted. 

Sizing & Selecting

Cooling Tower Selection Procedure

Example 2. Actual Design

Now we will select a cooling tower for the same 200-ton Nominal Load as Example #1 but is different from the Theoretical Design. The operating water flow rate is 300 GPM.

Hot water temperature (T1) to the cooling tower is 105° F.

Cold water temperature (T2) desired from the cooling tower is 85° F. The installation location's wet bulb temperature (Twb) is 76° F.

You can now make a cooling tower selection with this information:

The water flow is 300 GPM. The Range of cooling is 20° - (T1 - T2). The Approach to the wet bulb temperature is 9° - (T2 - Twb).

First, the cooling tower NOMINAL load must be determined:

Nominal Load = GPM x 500 x ° Range, = GPM x ° Range; therefore, 15,000 BTU/Hr 30.  Nominal Load = 300 gpm x 20° Range = 200 cooling tons required.  30 Since the Heat Load = Flow (gpm) x 500 x °Range of cooling= 300 gpm x 500 x 20° = 3,000,000 BTU/Hr and a cooling tower nominal ton = 15,000 BTU/Hr, the Nominal cooling tower ton is derived from the actual Heat Load. Again, a 3,000,000 BTU/Hr heat load = 200 Nominal cooling tower tons.

Now the Nominal Ton Correction Factor must be determined for the conditions established; a 20° Range of cooling, and a 9° Approach to the design wet bulb temperature of 76°F, using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed.

First, find the 20° Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the 20° Range line over to the intersection of the 76° Wet Bulb line. Move down along the 76° Wet Bulb line to the APPROACH SECTION, in the lower left-hand section of the chart, and stop at the intersection of the 9° Approach line. Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curves and stop at the intersection of the 20° Range line, and read the CAPACITY MULTIPLIER FACTOR, which in this case is 0.62.

The final step to select the proper cooling tower for this application is to multiply the 200 nominal cooling tons required, which was calculated above, by the CAPACITY FACTOR, which in this case is 0.62. The cooling tower Actual Rated tons for the conditions given are therefore 124 tons, and a Model DT-125I cooling tower can be quoted. Since the correction factor adjusts for the ease or difficulty of cooling based on the Theoretical Design, in this case, the Actual Rated tower conditions are easier than Theoretical Design.

Cooling Tower Selecting, Sizing, and Design

Find Your Optimal Cooling Tower Type

As the technology leading cooling tower manufacturer, Delta’s cooling tower designs last longer, save on costs and eliminate downtime, which translates to an unrivaled lifecycle. So, there’s no need to worry about replacements. And, Delta’s product quality is backed by a 20-year warranty. To learn more, contact Delta today. Click Here!

Explore Delta’s Cooling Tower Sizing Calculator

To determine the perfect cooling tower design and size for your needs, Delta makes it easy with our downloadable sizing program. To discover Delta’s cooling tower sizing & selection program, simply click here.

Narrowing Down Your Cooling Tower Selection

If you are interested in learning the methods of determining the proper size cooling tower, rest assured that Delta is here with guidance. Explore our handy information. Click here to learn about sizing & selecting.

Know Your Cooling Tower Capacity Calculation

Whether your application is for industrial process cooling or HVAC condenser cooling, the data required is the same. The following design data is required for cooling tower sizing to properly select the appropriate model:

  • Flow Rate in GPM
  • Range of cooling in °F (T1 – T2)
  • Area Wet Bulb Temperature in °F (Twb)

Cooling Tower Heat Load Calculation

The Design Heat Load is determined by the Flow Rate, and the Range of cooling, and is calculated using the following formula:

Heat Load (BTU/Hr) = GPM X 500 X Range (T1 – T2) °F

If the range of cooling, Heat Load, and one of the other two factors are known (either the GPM or the ° Range of cooling), the other can be calculated using this formula.

  • GPM = Heat Load (BTU/Hr) / 500 X ° Range of cooling
  • ° Range of cooling = Heat Load (BTU/Hr) / 500 X GPM The Design GPM and the °

The range of cooling is directly proportional to the Heat Load.

To learn more, contact Delta today. Click Here! 

Let Us Help You With Cooling Tower Sizing & Selecting

How comfortable are you working up a cooling tower selection?

The cooling tower selection table may look confusing, but after you have made a few selections, the process is straightforward. If you need a refresher, this may help. The following design data is required to select cooling towers:

Flow Rate in GPM

Range of cooling in °F (T1 - T2)

Area Wet Bulb Temperature in °F (Twb)

The Design Heat Load is determined by the Flow Rate, and the Range of cooling, and is calculated using the following formula: Heat Load (BTU/Hr) = GPM X 500 X ° Range of cooling.

More importantly, if the Heat Load and one of the other two factors are known, either the GPM or the ° Range of cooling, the other can be calculated using this formula.

For example: GPM = Heat Load (BTU/Hr), or 500 X ° Range of cooling ° Range of cooling = Heat Load (BTU/Hr) 500 X GPM

So, as you can see, the Design GPM and the ° Range of cooling, are directly proportional to the Heat Load.

And, 500 is the “fluid factor” which is based on water as the heat transfer fluid. The fluid factor is obtained by using the weight of a gallon of water (8.33 lbs.) multiplied by the specific heat of the water (1.0) multiplied by 60 (minutes/hour).

The first step in selecting a cooling tower is to determine the Nominal cooling tower load. Since a cooling tower ton is based on 15,000 BTU/Hr, the formula is:

Nominal Load = GPM X 500 (Constant) X ° Range of cooling, 15,000 BTU/Hr/Ton or, the more simplified version of the same formula, Nominal Load = GPM X ° Range of cooling 30

More on Sizing & Selecting

Examples of Different Applications

Once the Nominal cooling load has been calculated, a Correction Factor must be determined to calculate the Actual Rated cooling tower tonscooling tower tons required for the specific conditions of service. The correction factor adjusts for the ease or difficulty of cooling based on the Theoretical Design of all cooling towers.

The Nominal Ton Correction Factor is determined by using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed. Note that the curves are shown as three separate sections. The WET BULB CORRECTION SECTION, the APPROACH SECTION, and the CAPACITY MULTIPLIER FACTOR SECTION. First, find the Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the Range line over to the intersection of the Wet Bulb line.

Now move down along the Wet Bulb line to the APPROACH SECTION, in the lower left-hand section of the chart, and stop at the intersection of the Approach line. Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curves and stop at the intersection of the Range line and read the CAPACITY MULTIPLIER FACTOR.

The Actual Rated cooling tower tons can now be calculated by multiplying the Nominal cooling tons, which was previously calculated, by the CAPACITY MULTIPLIER FACTOR. The Actual Rated cooling tower tons is the capacity required for the specific conditions of service, and the next largest size cooling tower should be selected for the application.

Following are selection examples for three different applications. One example is based on conditions that are identified as "Theoretical Design," for reasons which will become apparent.

The second example, entitled "Actual Design" is a selection based on adjusting from Theoretical to Actual design.

The third example, "Modified Application", converts an actual once-through well water system to a cooling tower recirculation system.

Sizing & Selecting

Read on to Learn about Cooling Tower Selection Procedure

Example 1. Theoretical Design


The following conditions are provided for selection purposes:

The operating water flow rate is 600 GPM.

Hot water temperature (T1) to the cooling tower is 95° F.

Cold water temperature (T2) desired from the cooling tower is 85° F.

The installation location's wet bulb temperature (Twb) is 78° F.

You can now make a cooling tower selection with this information:

The water flow is 600 GPM. The Range of cooling is 10° - (T1 - T2). The Approach to the wet bulb temperature is 7° - (T2 - Twb).

First the cooling tower NOMINAL load has to be determined:

Nominal Load = GPM x 500 x ° Range, = GPM x ° Range, therefore, 15,000 BTU/Hr 30

Nominal Load = 600 gpm x 10° Range = 200 tons of cooling required.

30 Since the Heat Load = Flow (gpm) x 500 x °Range of cooling= 600 gpm x 500 x 10° = 3,000,000 BTU/Hr and a cooling tower nominal ton = 15,000 BTU/Hr, the nominal cooling tower ton is derived from the actual heat load. Therefore, a heat load of 3,000,000 BTU/Hr = 200 nominal cooling tower tons.

Now the Nominal Ton Correction Factor has to be determined for the conditions established:

A 10° Range of cooling, and a 7° Approach to the design wet bulb temperature of 78°F, using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed.

Find the 10° Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the 10° Range line over to the intersection of the 78° Wet Bulb line.

Move down along the 78° Wet Bulb line to the APPROACH SECTION, (the lower left-hand section), and stop at the intersection of the 7° Approach line.

Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curve and stop at the intersection of the 10°Range line, and read the CAPACITY MULTIPLIER FACTOR, which is 1.0.

To select the proper cooling tower for this application, multiply the 200 Nominal tons calculated, by the 1.0 CAPACITY FACTOR. As previously stated, the correction factor adjusts for the ease or difficulty of cooling in relation to the Theoretical Design. So in this case, since the CAPACITY CORRECTION FACTOR is 1.0, the Nominal and Actual Rated tons are the same as the Theoretical Design, and a Model DT-200I cooling tower can be quoted. 

Sizing & Selecting

Cooling Tower Selection Procedure

Example 2. Actual Design

Now we will select a cooling tower for the same 200-ton Nominal Load as Example #1 but is different from the Theoretical Design. The operating water flow rate is 300 GPM.

Hot water temperature (T1) to the cooling tower is 105° F.

Cold water temperature (T2) desired from the cooling tower is 85° F. The installation location's wet bulb temperature (Twb) is 76° F.

You can now make a cooling tower selection with this information:

The water flow is 300 GPM. The Range of cooling is 20° - (T1 - T2). The Approach to the wet bulb temperature is 9° - (T2 - Twb).

First, the cooling tower NOMINAL load must be determined:

Nominal Load = GPM x 500 x ° Range, = GPM x ° Range; therefore, 15,000 BTU/Hr 30.  Nominal Load = 300 gpm x 20° Range = 200 cooling tons required.  30 Since the Heat Load = Flow (gpm) x 500 x °Range of cooling= 300 gpm x 500 x 20° = 3,000,000 BTU/Hr and a cooling tower nominal ton = 15,000 BTU/Hr, the Nominal cooling tower ton is derived from the actual Heat Load. Again, a 3,000,000 BTU/Hr heat load = 200 Nominal cooling tower tons.

Now the Nominal Ton Correction Factor must be determined for the conditions established; a 20° Range of cooling, and a 9° Approach to the design wet bulb temperature of 76°F, using the COUNTERFLOW COOLING TOWER SELECTION AND PERFORMANCE CHART enclosed.

First, find the 20° Range line in the WET BULB CORRECTION SECTION in the upper left-hand section of the chart. Move along the 20° Range line over to the intersection of the 76° Wet Bulb line. Move down along the 76° Wet Bulb line to the APPROACH SECTION, in the lower left-hand section of the chart, and stop at the intersection of the 9° Approach line. Move across to the CAPACITY MULTIPLIER FACTOR SECTION to the right-hand curves and stop at the intersection of the 20° Range line, and read the CAPACITY MULTIPLIER FACTOR, which in this case is 0.62.

The final step to select the proper cooling tower for this application is to multiply the 200 nominal cooling tons required, which was calculated above, by the CAPACITY FACTOR, which in this case is 0.62. The cooling tower Actual Rated tons for the conditions given are therefore 124 tons, and a Model DT-125I cooling tower can be quoted. Since the correction factor adjusts for the ease or difficulty of cooling based on the Theoretical Design, in this case, the Actual Rated tower conditions are easier than Theoretical Design.

Sizing & Selecting

Cooling Tower Selection Procedure

3. Modified Application

The following is an example of modifying a "once through non-recirculating cooling application" to a recirculating cooling tower system. A cooling tower is required for heat exchanger process cooling, which is now being cooled using 55°F well water at a flow rate of (1 Million gallons/day - 300,000 sanitary = 700,000 gal per day).

Approximately 500 GPM, and discharging to a lake at 80°F. With this information we can establish the Heat Load, which is 500 GPM x 500 x 25° R (80°F - 55°F) = 6,250,000 Btu/Hr.

We can establish the cooling tower design for a 6,250,000 Btu/Hr Heat Load based on the installation location design Twb, which, for this example, we'll say is determined to be 76°F, and by establishing a reasonable cold water temperature at a 7° Approach to the Twb, at 83°F.

What we have to determine now is either the design range of cooling or the appropriate design flow rate based on the established Heat Load. Let’s select the appropriate design flow rate by using a reasonable 15° Range of cooling; 83°F cold water + 15° = 98°F hot water.

Use the Cooling Tower Heat Load Calculation to find the design flow rate as follows:

Heat Load (BTU/Hr) = GPM X 500 X ° Range of cooling, or rearranged to determine the design flow rate. GPM = Heat Load (BTU/Hr) = 6,250,000 Btu/Hr = 835 gpm 500 X ° Range of cooling 500 x 15° R Now you can make your cooling tower selection based on 835 gpm, cooling from 98°F to 83°F @ a design 76°F Twb. The cooling tower selection is = 418 Nominal Tons x .83 DCF = 347 Rated cooling tower tons, or a 350-ton cooling tower selection.

Alternate #1:

A cooling tower can also be selected for this heat load based on a 25° Range of cooling. The conditions for selection would be 500 GPM, cooling from 108°F to 83°F @ 76°F Twb, which is equal to 418 Nominal tons x .62 DCF = 259 Rated cooling tower tons, for a 260 ton cooling tower requirement.

Alternate #2:

Or select for a design to cool 110°F to 83°F = 27° R of cooling, the design flow would be 6,250,000 Btu/Hr = 465 GPM. 27° R x 500

The selection for 465 GPM cooling from 110°F to 83°F @ 76°F Twb = 418 Nominal tons x .58 DCF = 242 Rated tons; so you can recommend a single Model DT-250I cooling tower.

 

 

Water Treatment for Cooling Towers

Water treatment for cooling towers is vital to the safe and effective management of your cooling tower system.

As such, it's important to speak the language of cooling tower water treatment. We know cooling tower water treatment is important and why it's important, so let's dive into the lingo of cooling tower water treatment and take that understanding to the next level.

As such, we've compiled a list of some key terms for cooling tower water treatment. With that said, this is not an exhaustive list; cooling tower water treatment is a complicated and delicate science, so there are many more concepts worth understanding. 

Alkalinity

Alkalinity — or M-Alkalinity — is an important measurement for your cooling tower water treatment program of the amount of carbonates, bicarbonates and hydroxides in your process water.

Generally, you want your cooling tower process water on the alkaline side; however, if it is too alkaline, you can get deposition of scale (e.g., calcium carbonate). That's why cooling tower water treatment programs often include pH adjusters to bring pH down to optimal levels as needed, particularly as alkalinity levels increase as cycles of concentration increase. 

Biocides

Biocides are vital to any effective cooling tower water treatment program. Cooling towers offer a welcoming environment for microbial growth; if bacterial growth within the system is present, it could lead to fouling (see "Fouling" below), decreased efficiency and distribution of bacteria via aerosols that could lead to illness if inhaled. Perhaps the most well known example of this is Legionnaires' disease. 

So, biocides are the chemicals that mitigate and prevent microbial growth in your cooling tower system. These chemicals can be delivered in liquid or solid forms. 

Blowdown

Blowdown is the water flushed out of the system due to higher levels of mineral concentration. Simply put, the more cycles of concentration you can get out of your system, the more you save on water in the form of make-up water (see the "Make-up" entry below). 

Blowdown also includes leaks, drift and windage. 

Cooling Tower Basin

The cooling tower basin is where cooled process water is collected before it is recycled in the system. 

Corrosion

As with many industrial processes, corrosion is a cause for concern in the cooling tower system. Contaminants in the cooling tower system can lead to corrosion of various surfaces within the cooling tower. As a result, the heat-transfer capacity of the system and its efficiency declines. 

Counterflow

A counterflow cooling tower is a type of cooling tower in which air flows counter to the direction of the process water. 

Crossflow

Meanwhile, a crossflow cooling tower is a type of cooling tower in which the air moves horizontally with the direction of the process water.  

Cycles of Concentration

This term is one of the most important in the world of cooling tower water treatment. To calculate your cycles of concentration, you need to determine the ratio of dissolved solids in your blowdown water relative to your make-up water. 

"From a water efficiency standpoint, you want to maximize cycles of concentration," the Department of Energy explains. "This will minimize blowdown water quantity and reduce make-up water demand. However, this can only be done within the constraints of your make-up water and cooling tower water chemistry. Dissolved solids increase as cycles of concentration increase, which can cause scale and corrosion problems unless carefully controlled."

Drift

While much of the heat transfer in the system occurs via evaporation, some water is carried out via "drift," or by a mist or small droplets. Windage can be a contributor to drift. 

"Drift loss is small compared to evaporation and blowdown and is controlled with baffles and drift eliminators," the Department of Energy notes. 

Evaporation

The process by which most heat is transferred out of a cooling tower system. 

Fill

The cooling tower "fill" area is the surface on which the heated water is distributed as it enters the cooling tower system. From there, air contacts the water and heat is expelled from the system via evaporation. 

Fouling

Fouling is the general term for when material builds up and/or deposits on cooling tower surfaces, thus impacting the system's heat-transfer capacity. In addition to scaling, fouling is often referred to in the form of microbiological fouling, which is when microbial growth occurs within the system.

Cooling towers provide a welcoming environment — warm and wet — for microbial growth, which is why your cooling tower water treatment program must address the issue with the use of effective biocides. 

Heat Load

Heat load, measured in BTUs per hour, is the amount of heat that needs to be removed from the cooling tower process water. Heat load is an important parameter in determining tower size and cost. 

To determine heat load, multiply gallons per minute by 500 and by the temperature delta of cold water from the cooling tower and hot water going into the system. The formula is also written out below: 

Heat load=GPM x 500 x ΔT

Make-up

This term is related to the "blowdown" term above. Make-up water is exactly what it sounds like: it's the water used to make up for the loss in "blowdown" water.

In general, cooling tower water treatment seeks to make a more efficient process that leads to less need for make-up water. In short, an environmentally conscious and more sustainable process would call for less water.

As the Department of Energy explains, make-up is equal to the sum of blowdown, evaporation and drift in the system. However, as noted previously, when cycles of concentration increase, so does alkalinity and, in turn, the possibility of scaling.

pH

In most cooling tower systems, you will typically see a pH level of anywhere between 7.0-9.5. However, some systems do run outside of that range (i.e., more acidic or more alkaline). You don't want your process water to be too acidic, as that can lead to corrosion of various surfaces. However, if your process water is too alkaline, that can promote the formation of scale. Alkalinity in the water increases as evaporation occurs, meaning a rise in pH. 

Scale

When water is evaporated out of the system, remaining levels of solids can coat surfaces of the cooling tower, i.e., scale. What does that mean for the system and your cooling tower water treatment needs? Deposition of scale can negatively affect the heat-transfer capacity of the system. 

Furthermore, deposition of scale can also provide opportunity for microbial growth. 

In order to combat scale, you need scale inhibitors in your cooling tower water treatment program. 

Tons

Terms used to express the capacity or size of the cooling system. One ton is equivalent is equivalent to 12,000 BTU per hour. 

A ton of refrigeration represents the rate of cooling produced when a ton of ice that weighs 2,000 pounds melts during a 24-hour day. 

TDS (total dissolved solids)

Total dissolved solids represents the total amount of inorganic and organic molecules in the cooling tower process water. Those solids could include things like calcium, magnesium, silica and chloride, among others. Calcium carbonate is the most commonly found scaling deposit in the cooling tower system. 

In short, you don't want your TDS to get too high.

Think of a swimming pool. You and your family and friends are enjoying some time in the pool. There are a few pool toys floating around in there: a pool noodle or two, maybe a floating pool chair, a couple of smaller toys for the younger children. Bottom line, there's room for you to move around and enjoy the space offered by the pool. 

Now add, say, 30 more pool noodles, 20 more pool chairs and a flock of rubber ducks. There isn't as much space to move around and your pool experience isn't quite as enjoyable if you're constantly maneuvering around these various obstacles. Not only that, maybe all that flotsam and jetsam finds its way to the pool skimmers and drains, covering or clogging them up. If that happens — and you don't take time to address the problem — the pool system won't be able to effectively circulate clean, safe water for you to swim in. 

Meanwhile, if TDS gets too high in your cooling tower system, that means those solids could lead to corrosion, deposition of scale and microbial growth. That, in turn, contributes to lower heat-transfer capacity and a less efficient system. 

Water Balance/Mass Balance

Your make-up equals evaporation plus blowdown. 

Windage

Water lost from the cooling tower system when winds blows water droplets out of the cooling tower. 

Sizing & Selecting

Cooling Tower Selection Procedure

3. Modified Application

The following is an example of modifying a "once through non-recirculating cooling application" to a recirculating cooling tower system. A cooling tower is required for heat exchanger process cooling, which is now being cooled using 55°F well water at a flow rate of (1 Million gallons/day - 300,000 sanitary = 700,000 gal per day).

Approximately 500 GPM, and discharging to a lake at 80°F. With this information we can establish the Heat Load, which is 500 GPM x 500 x 25° R (80°F - 55°F) = 6,250,000 Btu/Hr.

We can establish the cooling tower design for a 6,250,000 Btu/Hr Heat Load based on the installation location design Twb, which, for this example, we'll say is determined to be 76°F, and by establishing a reasonable cold water temperature at a 7° Approach to the Twb, at 83°F.

What we have to determine now is either the design range of cooling or the appropriate design flow rate based on the established Heat Load. Let’s select the appropriate design flow rate by using a reasonable 15° Range of cooling; 83°F cold water + 15° = 98°F hot water.

Use the Cooling Tower Heat Load Calculation to find the design flow rate as follows:

Heat Load (BTU/Hr) = GPM X 500 X ° Range of cooling, or rearranged to determine the design flow rate. GPM = Heat Load (BTU/Hr) = 6,250,000 Btu/Hr = 835 gpm 500 X ° Range of cooling 500 x 15° R Now you can make your cooling tower selection based on 835 gpm, cooling from 98°F to 83°F @ a design 76°F Twb. The cooling tower selection is = 418 Nominal Tons x .83 DCF = 347 Rated cooling tower tons, or a 350-ton cooling tower selection.

Alternate #1:

A cooling tower can also be selected for this heat load based on a 25° Range of cooling. The conditions for selection would be 500 GPM, cooling from 108°F to 83°F @ 76°F Twb, which is equal to 418 Nominal tons x .62 DCF = 259 Rated cooling tower tons, for a 260 ton cooling tower requirement.

Alternate #2:

Or select for a design to cool 110°F to 83°F = 27° R of cooling, the design flow would be 6,250,000 Btu/Hr = 465 GPM. 27° R x 500

The selection for 465 GPM cooling from 110°F to 83°F @ 76°F Twb = 418 Nominal tons x .58 DCF = 242 Rated tons; so you can recommend a single Model DT-250I cooling tower.

 

 

Water Treatment for Cooling Towers

Water treatment for cooling towers is vital to the safe and effective management of your cooling tower system.

As such, it's important to speak the language of cooling tower water treatment. We know cooling tower water treatment is important and why it's important, so let's dive into the lingo of cooling tower water treatment and take that understanding to the next level.

As such, we've compiled a list of some key terms for cooling tower water treatment. With that said, this is not an exhaustive list; cooling tower water treatment is a complicated and delicate science, so there are many more concepts worth understanding. 

Alkalinity

Alkalinity — or M-Alkalinity — is an important measurement for your cooling tower water treatment program of the amount of carbonates, bicarbonates and hydroxides in your process water.

Generally, you want your cooling tower process water on the alkaline side; however, if it is too alkaline, you can get deposition of scale (e.g., calcium carbonate). That's why cooling tower water treatment programs often include pH adjusters to bring pH down to optimal levels as needed, particularly as alkalinity levels increase as cycles of concentration increase. 

Biocides

Biocides are vital to any effective cooling tower water treatment program. Cooling towers offer a welcoming environment for microbial growth; if bacterial growth within the system is present, it could lead to fouling (see "Fouling" below), decreased efficiency and distribution of bacteria via aerosols that could lead to illness if inhaled. Perhaps the most well known example of this is Legionnaires' disease. 

So, biocides are the chemicals that mitigate and prevent microbial growth in your cooling tower system. These chemicals can be delivered in liquid or solid forms. 

Blowdown

Blowdown is the water flushed out of the system due to higher levels of mineral concentration. Simply put, the more cycles of concentration you can get out of your system, the more you save on water in the form of make-up water (see the "Make-up" entry below). 

Blowdown also includes leaks, drift and windage. 

Cooling Tower Basin

The cooling tower basin is where cooled process water is collected before it is recycled in the system. 

Corrosion

As with many industrial processes, corrosion is a cause for concern in the cooling tower system. Contaminants in the cooling tower system can lead to corrosion of various surfaces within the cooling tower. As a result, the heat-transfer capacity of the system and its efficiency declines. 

Counterflow

A counterflow cooling tower is a type of cooling tower in which air flows counter to the direction of the process water. 

Crossflow

Meanwhile, a crossflow cooling tower is a type of cooling tower in which the air moves horizontally with the direction of the process water.  

Cycles of Concentration

This term is one of the most important in the world of cooling tower water treatment. To calculate your cycles of concentration, you need to determine the ratio of dissolved solids in your blowdown water relative to your make-up water. 

"From a water efficiency standpoint, you want to maximize cycles of concentration," the Department of Energy explains. "This will minimize blowdown water quantity and reduce make-up water demand. However, this can only be done within the constraints of your make-up water and cooling tower water chemistry. Dissolved solids increase as cycles of concentration increase, which can cause scale and corrosion problems unless carefully controlled."

Drift

While much of the heat transfer in the system occurs via evaporation, some water is carried out via "drift," or by a mist or small droplets. Windage can be a contributor to drift. 

"Drift loss is small compared to evaporation and blowdown and is controlled with baffles and drift eliminators," the Department of Energy notes. 

Evaporation

The process by which most heat is transferred out of a cooling tower system. 

Fill

The cooling tower "fill" area is the surface on which the heated water is distributed as it enters the cooling tower system. From there, air contacts the water and heat is expelled from the system via evaporation. 

Fouling

Fouling is the general term for when material builds up and/or deposits on cooling tower surfaces, thus impacting the system's heat-transfer capacity. In addition to scaling, fouling is often referred to in the form of microbiological fouling, which is when microbial growth occurs within the system.

Cooling towers provide a welcoming environment — warm and wet — for microbial growth, which is why your cooling tower water treatment program must address the issue with the use of effective biocides. 

Heat Load

Heat load, measured in BTUs per hour, is the amount of heat that needs to be removed from the cooling tower process water. Heat load is an important parameter in determining tower size and cost. 

To determine heat load, multiply gallons per minute by 500 and by the temperature delta of cold water from the cooling tower and hot water going into the system. The formula is also written out below: 

Heat load=GPM x 500 x ΔT

Make-up

This term is related to the "blowdown" term above. Make-up water is exactly what it sounds like: it's the water used to make up for the loss in "blowdown" water.

In general, cooling tower water treatment seeks to make a more efficient process that leads to less need for make-up water. In short, an environmentally conscious and more sustainable process would call for less water.

As the Department of Energy explains, make-up is equal to the sum of blowdown, evaporation and drift in the system. However, as noted previously, when cycles of concentration increase, so does alkalinity and, in turn, the possibility of scaling.

pH

In most cooling tower systems, you will typically see a pH level of anywhere between 7.0-9.5. However, some systems do run outside of that range (i.e., more acidic or more alkaline). You don't want your process water to be too acidic, as that can lead to corrosion of various surfaces. However, if your process water is too alkaline, that can promote the formation of scale. Alkalinity in the water increases as evaporation occurs, meaning a rise in pH. 

Scale

When water is evaporated out of the system, remaining levels of solids can coat surfaces of the cooling tower, i.e., scale. What does that mean for the system and your cooling tower water treatment needs? Deposition of scale can negatively affect the heat-transfer capacity of the system. 

Furthermore, deposition of scale can also provide opportunity for microbial growth. 

In order to combat scale, you need scale inhibitors in your cooling tower water treatment program. 

Tons

Terms used to express the capacity or size of the cooling system. One ton is equivalent is equivalent to 12,000 BTU per hour. 

A ton of refrigeration represents the rate of cooling produced when a ton of ice that weighs 2,000 pounds melts during a 24-hour day. 

TDS (total dissolved solids)

Total dissolved solids represents the total amount of inorganic and organic molecules in the cooling tower process water. Those solids could include things like calcium, magnesium, silica and chloride, among others. Calcium carbonate is the most commonly found scaling deposit in the cooling tower system. 

In short, you don't want your TDS to get too high.

Think of a swimming pool. You and your family and friends are enjoying some time in the pool. There are a few pool toys floating around in there: a pool noodle or two, maybe a floating pool chair, a couple of smaller toys for the younger children. Bottom line, there's room for you to move around and enjoy the space offered by the pool. 

Now add, say, 30 more pool noodles, 20 more pool chairs and a flock of rubber ducks. There isn't as much space to move around and your pool experience isn't quite as enjoyable if you're constantly maneuvering around these various obstacles. Not only that, maybe all that flotsam and jetsam finds its way to the pool skimmers and drains, covering or clogging them up. If that happens — and you don't take time to address the problem — the pool system won't be able to effectively circulate clean, safe water for you to swim in. 

Meanwhile, if TDS gets too high in your cooling tower system, that means those solids could lead to corrosion, deposition of scale and microbial growth. That, in turn, contributes to lower heat-transfer capacity and a less efficient system. 

Water Balance/Mass Balance

Your make-up equals evaporation plus blowdown. 